Biasi
Biasi boiler errors and error codes: a clear guide
Review the most common Biasi faults, what they indicate on the display, and when a reset is enough or technical inspection is needed.

In a Biasi boiler, the control panel doesn’t warn you for no reason: each code points to a specific fault in ignition, circulation, sensors, ventilation, or safety. Reading it correctly saves blind resets and helps isolate the problem before the breakdown gets worse.
If you have a problem with your boiler, you can use our free error code finder. From there, you can identify and fix all errors easily and effectively.
What the panel says when the boiler locks out
Biasi models with a digital display turn a fault into a readable message. On some units the warning appears as E01, E04, or E14; on others, especially when there is a remote control, the screen adds a letter or changes the format, but the logic remains the same. The electronics are telling you where to look first, not displaying a decorative message.
That difference matters because not all faults mean the same thing. A pressure problem is not interpreted the same way as a damaged sensor or an altered flue outlet. Correct reading narrows the search, avoids unnecessary part replacements, and reduces the risk of forcing components that are already operating at their limit. In a condensing boiler, where combustion, water, and electronics coexist, that detail makes all the difference.
It is also worth separating what a user can check cautiously from what requires a technician. A one-off lockout may be solved with a reset, but repeated faults are not normal. When the same code keeps coming back, there is usually an underlying cause: low actual pressure, air in the circuit, a tired pump, a sensor with erratic readings, or poor flue evacuation.
Other Biasi code formats: ER, A and longer E codes
Some older Biasi displays use ER codes, while particular ranges use A codes or longer E codes. These labels are not universal equivalents: check the manual for the exact model and serial range before applying a description from another range.
| Codes reported on particular ranges | Model-dependent meaning |
|---|---|
| ER 01, A01, E133 | Ignition failure or flame not detected. |
| ER 02, A02, E110 | Overheat or safety-thermostat lockout. |
| A03, E118 | Low primary-circuit pressure. |
| ER 05, A04, E154 | Fan or air-pressure monitoring fault, depending on the model. Possible causes also include the air-pressure switch, venturi or associated flue conditions. |
| ER 07, A07, E164 | Domestic hot-water sensor or temperature fault, depending on the range. |
| ER 09 | Flue-temperature sensor fault on some models. The sensor or associated flue-monitoring system requires professional diagnosis. |
| ER 69 | Wiring or electrical-control fault on some models. Connections, the control circuit or a component may be involved; do not remove the casing or test wiring. |
Do not shorten or substitute a displayed code. E133, for example, should not be interpreted by looking up E13. If the exact code is absent from a guide, use the appliance manual rather than borrowing a meaning from another model or manufacturer.
Table of the most common Biasi codes and faults
Biasi error codes are not a random list. In condensing units with self-diagnosis, the message is usually divided between lockouts that allow reset and faults that call for specialized service. In the most widely referenced model in the brand’s documentation, the display helps a lot in distinguishing both cases.
In practice, there are signs that accompany the code and guide the diagnosis: the word RESET, a flashing background, or a wrench icon. This visual clue, although simple, is very useful because it lets you know whether the unit has entered a recoverable lockout or an issue that should no longer be tackled from the panel.
| Code | Description | Cause | Type | What it usually means |
|---|---|---|---|---|
| E01 | Safety lockout due to ignition failure | No flame detected during start-up | User with reset | Check gas, ignition, or ionization |
| E02 | Lockout due to safety thermostat trip | Overtemperature or thermal protection activated | User with reset | Check circulation and temperature |
| E03 | Generic lockout | Non-specific error or safety condition without detail | User with reset | Used to restart and see if it reappears |
| E04 | Poor or no circulation, insufficient pressure, or pressure sensor not connected | Low pressure, pump problems, or lack of hydraulic reading | Technician | Check pressure, pump, and water sensor |
| E05 | Fan control anomaly | The fan does not spin, spins incorrectly, or does not communicate properly with the board | Technician | Combustion and flue safety |
| E06 | Heating flow NTC sensor fault | Incorrect outlet temperature reading | Technician | The boiler is measuring temperature incorrectly |
| E07 | DHW NTC sensor fault | Faulty or disconnected domestic hot water sensor | Technician | Unstable hot water or no service |
| E08 | External NTC sensor fault | Damaged outdoor sensor or no signal | Technician | It affects weather compensation control |
| E10 | Lockout due to tripping of flue probe and thermal fuse | Flue temperature above threshold | Technician | Check flue evacuation and combustion |
| E11 | Presence of stray flame | The electronics detect flame when they should not | Technician | Combustion control problem |
| E12 | Return NTC sensor fault | Return temperature reading is not reliable | Technician | May alter boiler modulation |
| E13 | Delta T M-R greater than 40 K | Anomalous difference between flow and return | Technician | Indicates circulation or heat transfer imbalance |
| E14 | Faulty pump or primary temperature above 105 °C | Circulation fails or temperature rises too much | User with reset or technician depending on recurrence | May also indicate lack of circulation due to a sudden rise |
| E18 | No heating delta T occurred during ignition | The system does not respond to thermal start-up | Technician | May point to pump, sensor, or flow rate |
| E19 | DHW inlet sensor anomaly | Incorrect hot water inlet sensor | Technician | Interferes with DHW stability |
| E20 | EVG lockout due to gas valve drive hardware fault | Fault in gas valve control | User with reset or technician | If it persists, professional diagnosis is required |
| E21 | EVG lockout due to gas valve control relay fault | Electrical control problem of the valve | Technician | Related to the electronics |
| E22 | Presence of flame after valve shutoff | Combustion does not stop as it should | Technician | This is a serious safety alarm |
| E23 | Gas valve modulator disconnected | Fault in the modulator or its connection | Technician | May affect flame adjustment |
| E24 | Possible flue blockage | Poor flue gas evacuation | Technician | Requires checking the duct and outdoor outlet |
| E25 | Flame loss more than 6 consecutive times | The boiler tries to ignite and switches off repeatedly | User with reset | There may be gas, ionization, or unstable combustion issues |
| E26 | Anomaly in maximum deviation between the two heating NTC sensors | The sensors do not match each other | Technician | Inconsistent temperature readings |
| E40 | Incorrect mains frequency | Electrical supply problem | Technician | May come from the installation or the grid |
| E42 | Button anomaly | Control panel with erratic pressing or signal | Technician | May affect operation of the unit |
| E44 | Accumulated timeout of the gas valve without flame | The gas sequence does not end in ignition | User with reset or technician | Sequence, ignition, or control failure |
| E50 | OT communication anomaly | Problem with the remote control or communication | Technician | May leave the unit without remote control |
| E62 | Calibration request | The boiler requests internal adjustment | Technician | Requires parameterization |
| E65 | System outside combustion control parameters | Modulation is not operating within range | Technician | Combustion check needed |
| E68 | Possible low gas pressure | Insufficient gas supply | Technician | The flame may become unstable |
| E77 | Modulator control outside parameters | Modulation control out of adjustment | Technician | It affects service stability |
| E78 | Possible low gas pressure | The supply does not meet the expected value | Technician | May recur together with other combustion warnings |
| E79 | Modulator control system outside parameters | Fault in the modulation circuit | Technician | Check gas and electronics |
| E89 | Internal error or problem in the electrical network | Hardware fault or distorted electrical signal | User with reset or technician | May appear after power incidents |
| E91 | Maximum permitted number of lockouts reached | Too many reset attempts | User with electrical restart | Unblocked with the procedure indicated by the brand |
| E99 | Boiler not configured | Missing parameterization or commissioning | Technician | Usually seen after installation or component replacement |
| Li | Primary NTC limitation in domestic water | Restriction in the primary sensor reading | Technician | Conditions DHW production |
| OFF | Boiler off with anti-freeze protection activated | Safe standby state | Normal | Not a fault, but a protection condition |
The table makes one important idea clear: not all warnings mean the same level of severity or the same type of intervention. Some codes suggest a quick check, while others point directly to sensors, fan, gas, flue, or electronics. In a real boiler, that nuance avoids confusion and unnecessary service calls.
Errors the user can try to reset
There are lockouts that Biasi’s own documentation places in a recoverable group via reset. They are not trivial faults, but they can stem from a temperature spike, a failed ignition attempt, or a safety protection being triggered. The screen usually shows the word RESET or a lockout status that is obvious at a glance.
Among the most representative codes are E01, E02, E03, E11, E14, E18, E20, E21, E22, E25, E44, E89, and E91. The user can reset the boiler in the cases предусмотрed by the manufacturer, but it should be done with judgment. If the fault keeps returning, it is no longer a simple one-off lockout, but a repeated signal that calls for finding the cause.
E01 usually refers to an ignition failure; E02, to a safety thermostat trip; E03, to a generic lockout; E11, to the presence of stray flame; E14, to a faulty pump or excessive primary circuit temperature; E25, to repeated flame loss. Each belongs to a different scenario, but they all share one thing: the boiler protects itself before continuing to operate under poor conditions.
E44, E89, and E91 also appear in this group. The first refers to an accumulated anomaly in the gas valve timing without flame; the second may respond to an internal fault or a distorted mains supply; the third indicates that the maximum number of lockouts has been reached. Do not overuse reset, because a reset button does not correct an underlying problem or replace a real inspection.
Warnings that usually require a technician
When the wrench icon appears on the screen, the message is no longer inviting the user to keep trying. The unit is saying that the problem affects a sensor, the flue, the fan, the gas valve, or internal communication. These are more delicate faults because they affect the basis of operation and, in many cases, safety.
This group includes E04, E05, E06, E07, E08, E10, E12, E13, E19, E23, E24, E26, E40, E42, E50, E62, E65, E68, E77, E78, E79, E99, and Li. The list is long, but not by chance: they are faults pointing to circulation, sensors, combustion, communication, or calibration. The symptom can be as visible as unstable hot water or as subtle as an out-of-range reading on the board.
A clear example is E04. It may mean poor circulation, insufficient pressure, or a disconnected water sensor. E05 focuses on the fan, an essential part in a sealed boiler. E06, E07, and E08 refer to NTC sensors, those small components that measure temperatures and allow precise control. If one of them fails, the boiler is working blind.
Other cases require even more caution. E10 and E24 have to do with flue gases and blockage; E23, E65, E68, E77, E78, and E79 focus on gas and modulation; E50, E62, E99, and Li usually appear when communication, calibration, or configuration are pending. These are warnings for technical diagnosis, not for home improvisation.
How reset is interpreted in a Biasi boiler
Reset is not a single action. In the brand’s condensing units, the documentation distinguishes several levels of reset. The first is the simplest: it restarts the boiler to clear certain recoverable lockouts. In many models, pressing the reset key is enough, sometimes integrated with standby, winter, or summer modes.
The second appears when the permitted attempts are exceeded. If the user-type lockout is not resolved and you keep trying several times, the boiler may end up showing E91. At that point, the reset involves a more complete procedure, which includes cutting and restoring power and following the sequence intended by the manufacturer. The idea is not to force the unit, but to return it to a stable state without bypassing the safety logic.
The third type of reset is even deeper and serves to restore factory values. It is not used for an everyday issue, but when the unit needs to return to previous parameters for adjustment or configuration. In the reference documentation, it is activated through an internal menu parameter, and confirmation is usually seen when all display symbols light up.
That technical detail, although it may seem minor, is very important. A factory reset is not a universal solution or a quick fix. It is used to reconfigure, not to mask a fault. If the problem returns shortly afterward, the root cause is somewhere else: pressure, pump, gas, combustion, sensors, or communication.
What symptoms help read the error more precisely
A lit screen says a lot, but the rest of the scene completes the diagnosis. If the boiler tries to start, you hear the fan, and then it locks out, the cause is usually in the ignition sequence or the flue path. If, on the other hand, the unit switches off shortly after operating, the focus may be on ionization, flame, or temperature. Sound also diagnoses.
When the fault coincides with cold radiators, it is worth thinking about circulation, pump, or pressure. If the hot water comes out irregularly, the problem may be in the DHW sensor, the three-way valve, or modulation. And if the issue appears right after several days of heavy use, accumulated temperature or poor evacuation may be the missing clue.
There are also less obvious signs. An unstable electrical supply, a remote control that loses communication, or a button that responds badly can lead to codes such as E40, E42, or E50. They may seem less dramatic, but they have a real impact on daily operation. The boiler, after all, needs all its parts to speak the same language.
At this point, it is worth remembering something practical: the code is not the whole problem, but the most visible warning. A serious reading combines number, context, and behavior. An E14 in a house with low pressure and half-empty radiators is not interpreted the same way as an E14 in an installation with a noisy pump and a very hot casing.
What to check without entering risky territory
Before thinking about a repair, there are sensible checks that do not require dismantling anything. Circuit pressure is one of them. In many domestic installations, when cold, it is usually around 1 to 1.5 bar, although the correct value should still be taken from the manual for the specific model. If it is low, the boiler may lock out for protection.
Gas and electricity supply also deserve attention. A half-closed valve, an empty cylinder, a power cut, or an unstable electrical connection can trigger a lockout code even when there is no serious fault behind it. The basics are still the basics: gas, pressure, power, and flue outlet.
If heating does not respond, bleeding radiators can help recover some circulation when there is air in the system. It will not fix a faulty pump or a defective sensor, but it does remove a common cause of poor heat transfer. By contrast, opening the casing, handling the gas valve, or touching the combustion circuit is a different matter.
When there is a smell of gas, unusual noise, repeated RCD trips, flue stains, or abnormal temperature on the boiler body, caution is no longer just a suggestion. In those cases, insisting with resets or forcing the start-up can make things worse. The electronics protect before the damage is visible, and that protection deserves respect.
The faults that repeat most often and why they come back
Some errors reappear because they affect weak points in any system. Low pressure can hide small leaks, recent bleeding, or a tired expansion vessel. Lack of circulation is often linked to worn pumps, dirt in the circuit, or trapped air. And thermal instability points to NTC sensors that no longer measure accurately.
In combustion, the range is also broad. An ignition failure does not always originate in the burner; sometimes it is in the gas supply, the spark, ionization, or the board itself. The fan, air pressure switch, and flue sensor form a very sensitive chain. If one link fails, the boiler stops before risking incorrect combustion.
That is why Biasi codes should be read as part of a story and not as isolated sentences. An E04 points to circulation and pressure; an E05 leads to the fan; an E10 looks at flue gases; an E14 requires checking pump and temperature; an E65 or E79 places the focus on modulation. Each message narrows the map, but a complete diagnosis requires seeing the whole sequence.
The advantage of this system is clear: the user no longer moves blindly. The disadvantage also exists: interpreting the message correctly requires context. The same number can hide several scenarios, and the same fault can present itself differently depending on the model, the installation, or the connected control. That is where technical reading becomes valuable.
What to record before calling an engineer
Write down the complete display message, including letters, spaces and flashing indicators. A photo helps distinguish similar characters. Identify the exact model from the user documents or an accessible label, without removing the casing.
- Record whether heating, hot water or both have stopped.
- Note whether the fault began after a power interruption or a change in system performance.
- Look for visible water around accessible pipework without loosening fittings.
- Keep a dated record of recurring codes and symptoms to share with the engineer.
For an ignition warning, noting whether other gas appliances are working can provide useful context, provided there is no suspected gas leak. This is an observation, not a reason to adjust gas controls.
Gas emergencies, flue access and frozen condensate pipes
If you smell gas, leave the area and follow the emergency instructions for your location. Do not use switches or flames in the affected area. In the United Kingdom, call the National Gas Emergency Service on 0800 111 999 from a safe place.
An external flue outlet may be observed from a safe position, but do not reach into it, remove covers, climb to it or attempt to clear an obstruction that requires tools or access to the flue. An apparently blocked outlet needs inspection by an appropriately qualified engineer.
If a condensate pipe appears frozen, consult the model instructions or a qualified professional before acting. Do not use boiling water or heat-producing equipment near the boiler or pipework, and do not climb to reach it.
Smoke or combustion smells indoors require prompt attention. Stop operating the appliance and seek qualified help; do not restart an appliance that may be releasing combustion products into the home. In the UK, gas-appliance work must be carried out by an engineer registered for gas work.
Separate symptoms on Biasi solid-fuel appliances
Biasi has also made other types of heating appliance. References to ash collection or a draft regulator concern certain solid-fuel designs and should not be interpreted through the gas-boiler code table.
| Symptom | Possible cause on certain solid-fuel appliances | Limit of user action |
|---|---|---|
| Dark smoke | Restricted flue path, a dirty appliance or a full ash collection area. | Use the appliance-specific instructions; do not dismantle the flue. |
| The appliance does not heat | A draft-regulator or combustion-air issue. | Do not adjust combustion settings unless the manual explicitly identifies a user control. |
| Smell of combustion products | Smoke escaping into the room, potentially associated with a door or combustion-chamber seal. | Stop using the appliance, ventilate if safe and arrange an urgent professional safety inspection. |
Repair costs and when replacement becomes a consideration
A code alone cannot establish a repair price. Diagnostic time, local labor rates, parts availability and the extent of the work all affect the bill. Published third-party UK estimates provide the following broad examples, not official Biasi prices or guaranteed current quotations.
| Repair or work | Indicative published UK range |
|---|---|
| Ignition electrode replacement | £120–£220 |
| Gas valve replacement | £250–£450 |
| Pump replacement | £280–£420 |
| Fan replacement | £220–£380 |
| Air-pressure switch replacement | £120–£200 |
| Sensor replacement | £140–£250 |
| Power flush | £350–£600 |
Ask for an explanation of the diagnosis and proposed work, and confirm that the required parts are available before committing to extensive repairs. Actual quotations depend on the model, location, parts and labor.
An isolated fault does not automatically justify replacement. Replacement becomes a broader consideration when reliability declines, faults recur, parts become difficult to obtain or repair costs accumulate. Age, condition, repair history and expected future reliability matter more than one displayed code.
The real usefulness of these codes in a modern boiler
In a home, the boiler usually goes unnoticed until it stops working. That everyday silence is deceptive, because inside the unit water, gas, heat, pressure, and electronics are combined in a mix that leaves very little room for error. Fault codes break that silence and turn it into useful information.
Read calmly, they let you distinguish the everyday from the serious: low pressure, air in the circuit, a tired pump, a misadjusted sensor, broken communication, or compromised flue evacuation. The difference between a minor fault and a prolonged shutdown is often in acting in time, not in pressing the same button several times.
The best response to a repeated code is to interpret it as a meaningful signal, not as a nuisance. The boiler has already spoken. Listening methodically, respecting its safety lockouts, and leaving complex repairs to qualified professionals is, almost always, the wisest way to restore comfort without adding new damage.
In Biasi, the panel is not there to decorate the kitchen or utility room. It is there to warn with precision. And when the message is properly understood, the fault stops being a vague shadow and becomes what it really is: a contained, diagnosable problem, and in many cases, perfectly solvable.
This article contains affiliate links: if you buy through them, we earn a small commission at no extra cost to you. More information.
Coffee machine6 days agoPhilips coffee machine error 05: what it means and what to do
Magazine2 days agoReplacing boilers with heat pumps: CAE multipliers up to x6
Coffee machine6 days agoPhilips coffee machine error 1: causes and safe cleaning
Daikin6 days agoDaikin heat pump error codes: meanings and safe checks
Magazine6 days agoMan affected by smoke in Valladolid fire
Magazine6 days agoXiaomi launches steam air fryer in Spain for €179.99
Air fryer6 days agoCecotec air fryer E1 error: what to do safely
Magazine5 days agoHow to Clean a Washing Machine and Fridge: Samsung’s Guide
Heat pump6 days agoMitsubishi Ecodan heat pump error codes: causes and fixes
Heat pump5 days agoHitachi heat pump error codes: meanings and safe solutions
Magazine4 days agoENISA warns home appliances could be the next cyberattack target
Boiler5 days agoImmergas boiler error codes: meanings and safe solutions





















